The DZ47LE-63 Residual Current Circuit Breaker is designed for AC 50Hz/60Hz systems, providing protection against electric shock, overload, and short circuits. It supports voltages of 230V/400V and currents up to 63A. The device complies with GB16917.1 and IEC61009-1 standards, ensuring safety in residential environments and has obtained CCC certification.
The DZ47LE-63 Residual Current Circuit Breaker is manufactured in China and designed for AC 50Hz/60Hz systems with rated voltages of 230V/400V and currents up to 63A. This reliable device provides protection against electric shock, overload, and short circuits, ensuring personal safety and preventing equipment damage from leakage currents. It also offers optional voltage protection against grid overvoltage upon request. As a trusted supplier and factory, we ensure high-quality manufacturing for optimal performance and safety.
Advantages
1.Comprehensive Protection: Offers protection against electric shock, overload, and short circuits, ensuring user safety and equipment integrity.
2.Optional Voltage Protection: Can be customized with additional voltage protection to guard against overvoltage due to grid faults.
3.Versatile Use: Suitable for residential buildings and similar environments, providing reliable performance in everyday applications.
4.Compliance with Standards: Meets GB16917.1 and IEC61009-1 standards, ensuring high-quality safety and performance.
5.CCC Certification: Certified product that guarantees adherence to safety regulations.
MAIN TECHNICAL PARAMETERS
Maximum rated current A of the frame size.
Number of poles
With neutral line.
Rated Current In (A)
Rated Voltage Un (V)
Rated residual operating current
Rated residual non-operating current
Breaking time
Rated residual making and breaking capacity I△m (A)
Overcurrent Instantaneous Trip Type
32
1
+N
610162025
230
3050100300
152550150
<0.1
2000
CD
2
230
3
400
3
+N
400
4
400
63
1
+N
32405063
230
2
230
3
400
3
+N
400
4
400
Rated short-circuit capacity Icn, service short-circuit breaking capacity Ics.
Project
Rated Current
Rated Short-Circuit Current (A)
Service Short-Circuit Breaking Capacity (A)
DZ47L
6~63A
4500
4500
DZ47LH
6~63A
6000
6000
Overcurrent protection characteristics at 30°C~35°C.
Rated current of the trip unit (A)
Initial State
Test Current
Required Time
Outcome
Notes
6~63
Cold state
1.13In
t≤1h In ≤ 63A
No trip
6~63
Proceed immediately after the previous test
1.45In
t<1h In ≤ 63A
trip
The current increases steadily to the specified value within 5 seconds.
In ≤ 32
Cold state
2.55In
1s
trip
In ≤ 32
Cold state
2.55In
1s
trip
6~63
Cold state
5In10In
t ≤ 0.1st<0.1s
No trip
Type C
10In14In
t ≤ 0.1st<0.1s
No trip
Type D
Main Features
1.Operating Specifications: Designed for AC 50Hz/60Hz systems with a rated operational voltage of 230V/400V and a rated current up to 63A.
2.Leakage Current Protection: Prevents damage from leakage currents, enhancing overall safety.
3.Short-Circuit and Overload Protection: Provides additional protection for electrical circuits, ensuring system reliability.
4.Infrequent Switching Capability: Can be used for occasional switching operations under normal conditions, adding to its versatility.
5.User-Friendly Installation: Designed for easy installation in residential and similar settings.
<
Product Highlights
1.Integrated Earth Leakage Protection: Combines residual current protection, overload protection, and short-circuit protection in one unit for comprehensive electrical safety.
2.Multiple Earth Leakage Trip Settings: Supports various trip currents such as 30mA, 50mA, 100mA, and 300mA to suit different application scenarios.
3.Compact Modular Design: Width only 36mm for 2P and 72mm for 4P, saving space in distribution boards for a neat installation.
4.High Breaking Capacity Options: Standard breaking capacity 4.5 kA, high breaking capacity up to 6 kA, suitable for different short-circuit risk environments.
Production Process Advantages
1.Fully Automated SMT Production Line: Electronic PCBs use automated SMT soldering for high consistency and reliability.
2.Dual Functional Testing: Each unit undergoes electrical characteristic tests and earth leakage protection accuracy calibration.
3.Eco-Friendly Material Application: Housing materials are recyclable, production is lead-free and halogen-free, meeting green manufacturing standards.
4.Full-Process Quality Traceability: Barcode management system enables traceability from raw materials to finished products.
Innovation Highlights
1.Independent Circuits for Earth Leakage and Overcurrent Protection: Two protection systems operate without interference, enhancing overall reliability.
2.Harmonic Interference Resistance: Optimized filtering circuitry reduces harmonic impact on earth leakage detection, preventing false tripping.
3.Self-Locking Test Button: Test button with self-locking function prevents accidental tripping from unintended pressing.
4.Optional Overvoltage Protection Module: Can be equipped with an overvoltage trip accessory for grid overvoltage protection.
Why Choose Us
1.Specialized Earth Leakage Protection Manufacturer: Jinhand Electric has years of R&D and production experience in residual current protection.
2.Complete Certification Portfolio: Products certified by CCC, CE, etc., compliant with GB 16917.1 and IEC 61009-1 standards.
3.High Cost-Effectiveness: Significant price advantage for equivalent performance, helping customers control costs.
4.Rapid Response Service System: Provides one-stop services from selection and installation to after-sales support with timely technical assistance.
FAQ
1. Does it support DC earth leakage protection?
This series is for AC residual current protection; DC systems require dedicated DC earth leakage protection devices.
2. Must the neutral wire pass through the transformer during installation?
For 1P+N and 3P+N models, the neutral wire must pass through the transformer together with the phase conductors; otherwise, earth leakage protection will be ineffective.
3. Is it suitable for TT and TN systems?
Suitable for TT, TN-C-S, and TN-S systems; refer to the product manual for specific wiring methods.
4. Does it support remote tripping?
Standard models do not; remote electrical tripping can be achieved by customizing a shunt trip accessory.
Customer Feedback
1."Selected the DZ47LE-63 series for multiple residential district power distribution renovation projects. Sensitive earth leakage protection, easy installation, effectively improving electrical safety."
2."High cost-performance ratio, complete specifications, especially suitable for export projects with strict certification requirements for earth leakage protection."
Contact us
After over a decade of progressive growth, Jinhand has emerged as one of the top manufacturers and suppliers of electrical equipment in China. Our factory is equipped with numerous cutting-edge technologies and machinery, and we welcome you to buy our top-quality, reasonably priced products made in China.
Hot Tags: Residual Current Circuit Breaker, China, Manufacturer, Supplier, Factory
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies.
Privacy Policy